Comment by John Hoffman on December 10, 2009 at 19:20
Mathew it looks to be a good solution, did you have : racks frames or cabs? How did you solve the probs that you found during the install? I am very interested in you recent install any details welcome. What prompted the change.
Comment by Mathew Hawkins on November 21, 2009 at 21:45
We are just installing these in some of our data centres.
Comment by John Laban on April 15, 2009 at 22:50
Dave

How high is the void in the access ceiling?

John
Comment by Dave Needham on March 16, 2009 at 12:31
Butch
We have not perceived any fire code issues but you must ensyre the following.

1) The PVC should be fire retardant and anti static.
2) The fire alarm should be tested to ensure it is loud enough within the cold aisle to meets current regulations

Post installation, we also had a fire assessment from our fire specialists to ensure it did not contravene any other regulations.

The only issue seemed to be on the delivery of the fire extinguishing gas but it was confirmed that our CRAC units do not switch off during gas release therefore dispersion within the cold aisle should not be affected ( especially as the system was to be run in manual)

Regards
Dave
Comment by butch adkins on March 10, 2009 at 21:04
Are there fire code issues with using this method?